Reliable Single Interlock Preaction System Servisní příručka

Procházejte online nebo si stáhněte Servisní příručka pro Detektory kouře Reliable Single Interlock Preaction System. Reliable Single Interlock Preaction System Technical data Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 36
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 0
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Bulletin 700
Bulletin 700
Special Hazards
and
Special Systems
INTRODUCTION
This manual has been prepared by The Reliable Automatic Sprinkler Co., Inc. to provide a comprehensive source of
information that will help users select and purchase Deluge, Preaction, and Low Pressure Dry Systems for a wide variety
of fire protection applications. This manual is complemented by other Reliable Automatic Sprinkler Company bulletins
that provide instructions for installation, operation and maintenance of the various systems.
Referencing the Table of Contents, Section 1 of this manual describes different types of special systems and provides
guidance on selection and application. Section 2 provides technical data on the components manufactured and/or dis-
tributed by Reliable for use in special systems, and Section 3 provides a work sheet to simplify ordering procedures for
the systems described in the manual.
Our objective is that users of this bulletin find the information beneficial and arranged in a user-friendly manner. Respon-
sibility for the actual design and installation of any fire sprinkler system rests with the engineer of record, certified layout
technician and/or the Authority Having Jurisdiction.
Zobrazit stránku 0
1 2 3 4 5 6 ... 35 36

Shrnutí obsahu

Strany 1 - Special Systems

Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523Bulletin 700Bulletin 700Special HazardsandSpecial SystemsINTR

Strany 2 - TABLE OF CONTENTS

1.2.2 Model DDX Dry Pilot Line Single InterlockWhere freezing conditions exist, or where height/distance limits of wet pilot lines are exceeded, a dr

Strany 3 - 1. SYSTEM DESCRIPTIONS

11.1.2.3 Model DDX Electrical Actuation Single InterlockWhere electrical actuation of the system is preferred over wet or dry pilot lines, or where o

Strany 4

1.2.4 Model H Single Interlock Preaction SystemThe Reliable Model H 1-1/2” (40mm) Single Interlock Preaction system is an electrically actuated sys-t

Strany 5

13.1.3 Double Interlock Preaction Systems Double interlock preaction systems are designed to protect water sensitive environments where the inadver-t

Strany 6

1.3.1 Model DDX Type DThe Reliable Type D Double Interlock Preaction system utilizes a listed, normally closed (de-energized) electric solenoid valve

Strany 7

15.1.3.2 Model DDX Type F The Reliable Type F Double Interlock Preaction system utilizes a Model LP Dry Pilot Actuator down-stream of a listed, norma

Strany 8

1.3.3 Model DDX Type PLThe Reliable Type PL Double Interlock Preaction system utilizes an LPDI Double Interlock Actuator on the outlet of the Model

Strany 9

17. 1.3.4 Model H Type DThe Reliable Model H 1-1/2” (40mm) Double Interlock Preaction System Type D is an electrically actu-ated system that utilizes

Strany 10

1.4 Non Interlock Preaction SystemNon-interlock preaction systems combine the operational features of a single interlock preaction system and a dry s

Strany 11

19. 1.5 Low Pressure Dry System Low pressure dry pipe systems offer numerous advantages over conventional systems. Conventional dif-ferential dry pipe

Strany 12

TABLE OF CONTENTS 1. SYSTEM DESCRIPTIONS1.1 Deluge Systems1.1.1 Model DDX Wet Pilot Line Trim 1.1.2 Model DDX Dry Pilot Line Trim 1.1.

Strany 13

1.5.1 Reliable Model EX Dry SystemThe Reliable Model EX Dry system utilizes a dry pilot actuator directly mounted to the push-rod cham-ber of a Model

Strany 14

1.5.2 Reliable Model DDX-LP Dry SystemThe Reliable Model DDX-LP Dry system utilizes a Model LP Dry Pilot Actuator as the releasing device on the outle

Strany 15

1.6 PrePak & DryPak Reliable PrePaK Preaction and DryPak Low Pressure Dry systems are completely self-contained riser assem-blies that can be rea

Strany 16

23.2. COMPONENT DESCRIPTIONS2.1 Main System Control Valves Special systems, whether deluge, preaction or low pressure dry, control the release of wat

Strany 17

2.1.2 Model DDX The Reliable Model DDX Deluge Valve is a hydraulically-operated, differential-type, latching valve with external reset designed for u

Strany 18

25.Alarm devices are activated via the alarm port upon flow of water into the sprinkler system piping. Once the flow of water has stopped, the clapper

Strany 19 - 1.5 Low Pressure Dry System

An external reset knob on the back left hand (pushrod) side of the Model DDX Deluge Valve allows the user to reset the valve without removing the face

Strany 20

2.2 Releasing Devices A releasing device serves to vent hydraulic pressure from the main system control valve push-rod chamber allowing the Model DDX

Strany 21

2.2.3 Solenoid ValveA normally closed electric solenoid valve is a primary control valve releasing device when located on the discharge outlet of the

Strany 22 - 1.6 PrePak & DryPak

29.2.3.1 Air Compressor PanelReliable Model B-SI and C-SI Air Compressor Panels provide self-contained supervisory air supply and pressure maintenanc

Strany 23 - 2. COMPONENT DESCRIPTIONS

3.1. SYSTEM DESCRIPTIONS1.1 Deluge Systems A deluge system utilizes open sprinklers or nozzles and non-pressurized system piping. When a deluge syst

Strany 24

30.2.3.3 Compressed NitrogenCylinders of compressed nitrogen can provide a clean, dependable, and most importantly, dry source of pneumatic pressure

Strany 25

31.Figure 33MODEL A-2Figure 34MODEL B-1 2.4.2 Model B-1 Air Maintenance DeviceThe Reliable Model B-1 Pressure Maintenance Device is designed for use

Strany 26

32.2.4.4 Nitrogen Regulating DeviceThe Reliable Nitrogen Regulating Device is used to regulate pressure to individual or multiple preac-tion and dry

Strany 27 - 2.2 Releasing Devices

33.2.5.2 Model EPS10 Pressure SwitchThe System Sensor Model EPS10 pressure switch is used for single interlock preaction systems and Reliable Type D

Strany 28

34.The alarm continues to sound as long as pressurized water is in the sprinkler system and will stop when the main water supply control valve is clos

Strany 29

35.GroovedxGrooved(AllSizes)FlangedxGrooved(4"&6"SizesOnly)FlangedxFlanged(4",6",&8"Sizes

Strany 30

Reliable Automatic Sprinkler Co., Inc.(800) 431-1588 Sales Offices(800) 848-6051 Sales Fax(914) 829-2042 Corporate Officeswww.reliablespri

Strany 31

1.1.1 Model DDX Wet Pilot Line TrimA wet pilot line is a non-electrical type of detection/release system that can be used in conditioned (i.e. freeze

Strany 32

5.1.1.2 Model DDX Dry Pilot Line TrimWhere freezing conditions exist, or where height/distance limits of wet pilot lines are exceeded, a dry pilot li

Strany 33 - 2.6 Quick-Opening Device

1.1.3 Model DDX Electrical Actuation TrimWhere electrical actuation of the system is preferred over wet or dry pilot lines, or where otherwise re-qui

Strany 34 - 3. ORDERING GUIDE

7.1.1.4 Model H Deluge Riser AssemblyThe Reliable Model H 1-1/2” (40mm) Deluge Riser Assembly is an electrically actuated system that utilizes a norm

Strany 35 - GENERALINFORMATION

1.2 Single Interlock Preaction Systems A single interlock preaction system is best described as a dry pipe system that is converted to a wet pipe sys

Strany 36 - (800) 848-6051 Sales Fax

9.1.2.1 Model DDX Wet Pilot Line Single InterlockA wet pilot line is a non-electrical type of detection/release system that can be used in conditione

Komentáře k této Příručce

Žádné komentáře