The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Single Interlock
Electric Release
Preaction System
2” (50mm), 2
1
/
2
” (65mm),
3” (80mm) & 76mm Sizes
Bulletin 736 Rev. B
Bulletin 736 Rev. B
Instructions for
Installation, Operation,
Care and Maintenance
2 PSI (0,14 bar) Pneumatic Supervising
Pressure with Electric Actuation
Available with 175 psi (12,1 bar) or
250 psi (17,2 bar) Rated Solenoid
Valve
Externally Resettable Clapper
One Main Drain
Zobrazit stránku 0
1 2 3 4 5 6 ... 19 20

Shrnutí obsahu

Strany 1 - Care and Maintenance

The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523Single InterlockElectric ReleasePreaction System2” (50mm)

Strany 2 - Listings & Approvals

10.ampere-hour rating, providing [60 hours – cULus Listed] [90 hours – FM Approved]. Dry contacts shall be provided for remote annunciation of alarm,

Strany 3

With the Model B Manual Emergency Station, valve D (Fig. 6), open, push in and rotate the Deluge Valve’s external reset knob (#14, Fig. 5) clockwise u

Strany 4

12.Fig. 5

Strany 5 - System Operation

13.Models DDX 2” (50mm), 2½” (65mm) 3” (80mm) & 76mm Deluge Valve Parts ListItemNo.Part NumberPart DescriptionNo. Req’d2” Valve 21/2” Valve 3” Va

Strany 7

15.Maintenance Procedures - Model DDXDeluge Valve Refer to Figs. 2, 5, & 6.Mechanical sprinkler alarm (water motor–not shown) not operating: This

Strany 8

16.Shut down the valve controlling water supply to the Deluge Valve. Relieve the inlet pressure by opening the 1¼” drain valve B (Fig. 6). Close the v

Strany 9 - Optional System Accessories

17.Ordering InformationSpecifyValve Model & Size — 2” (50mm) Model DDX Deluge Valve (P/N 6103022000), 2½” (65mm) Model DDX Deluge Valve (P/N 61030

Strany 11 - Without Flowing Water

19.Installation Dimensions in Inches (mm)VALVE A B C *D E F G H J K L M N P Q R2” (50mm)2½” (65mm)3” (80mm)& 76mm73/4”(197)61/4”(159)8(203)121/2”(

Strany 12

2.General Description Single Interlock Preaction Systems are designed for wa-ter-sensitive areas that require protection from inadvertent water flow i

Strany 13

The Reliable Automatic Sprinkler Co., Inc.(800) 431-1588 Sales Offices(800) 848-6051 Sales Fax(914) 829-2042 Corporate Officeswww.reliable

Strany 14

3.Fig. 1

Strany 16

5.System OperationTo fully operate a Single Interlock Preaction System, two independent events must coexist before water flow will oc-cur. One electr

Strany 17 - Ordering Information

6.After system shutdown, resetting the Model DDX Deluge Valve is quite simple. Doing so only requires pushing in and turning the reset knob at the re

Strany 18

7.System Air Pressure RequirementsA Reliable Model B Air Compressor Panel or Model C Pressure Maintenance Device is used to maintain the sys-tem pneum

Strany 20 - (800) 848-6051 Sales Fax

Single Interlock Preaction System– Electric Release Trim Engineering Specifi cations General DescriptionPreaction system shall be a Single Interlock Pr